• About
    • Our Team
    • Location
    • Industry Case Studies
    • Mission & Values
    • Corporate Responsibility
    • Vendor Management
    • History
    • Contact
  • Industries
    • Agribusiness
    • Food & Beverage
    • Metals & Steel
    • Mining, Aggregate, & Concrete
    • Oil & Gas
    • Paper
    • Power Generation & Energy
    • Water & Wastewater
    • Wind Services
  • Products
    • Type
    • Manufacturers
    • Asset Management Program
  • Generators
  • Remanufacture
    • Electrical Repairs
    • Mechanical Repairs
    • Machining
  • Field Services
    • All Services
    • Installation and Commissioning
    • Overhead Crane & Hoist Services
    • Wireless Equipment Condition Monitoring IoT
    • Predictive & Preventative
      • Vibration Analysis
      • On-Site Electrical Testing
      • Large AC and DC Motor PM and Repair
      • Gear Reducers
      • Precision Laser Alignment
  • Asset Management
    • Asset Management Program
    • Transport & Logistics
  • Careers
  • Login

Decatur Industrial Electric

Contact Us

Service & Quotes: 217-428-6621

You are here: Home / Archives for Electric Motors

Winter Weather Considerations

Even in the winter months a motor can overheat. Especially if snow or ice covers the air vents and prevents air from circulating on open drip proof designs. Motors running at design temperature should have an average insulation life expectancy of 20,000 running hours. Running motors hotter than design will reduce insulation life and running motors cooler than design will increase insulation life.

Not all motors have the luxury of being installed into a nice cool winter environment, so a review of the design temperature is important. Most motors have an ambient temperature rating of 40°C and an insulation class (A,B,F or H) listed on the motor nameplate. If your motor nameplate says insulation class B you can open your Electrical Engineering Pocket Handbook by EASA and see the temperature rating for Class B insulation is 130°C. So how does 130°C insulation rating and 40°C ambient temperature rating relate? Well, this means that if you start your motor with an ambient (outside air) temperature of 40°C, the internal insulation temperature should not exceed the insulation rating of 130°C. In a T-Frame Totally Enclosed Fan Cooled motor with Class B insulation an 80°C temperature rise is expected. Temperature Rise is the differential temperature from the ambient temperature and the internal winding temperature. So at full load and 40°C ambient with an 80°C rise, the surface temperature could reach 120°C (40°C+80°C). The 10°C difference (120°C vs. 130°C) is for hot spot allowance that may occur deep in the stator winding slots.

Even in winter months don’t be too quick to test the surface temperature of your motor with a bare hand. Surface temperature depends on many cooling design factors, but for a standard T-Frame motor, surface temperatures may reach as high as 95°C (203°F) and still be considered normal. Ouch! So don’t let snow and ice cover air vents and do be careful what you touch.

To see what happens to overheated insulation visit the PdMA YouTube Channel at: https://www.youtube.com/watch?v=Vt0cO1jHnKA 

Source: PdMA

Filed Under: Electric Motors

Look for the Swirl

For many people the word “swirl” creates visions of whirlpools, storm winds, or even ice cream cones. But if you have been in the reliability industry, and specifically the electrical reliability industry, the word swirl means something totally different. The late G.B. Kliman is credited for much of the research documentation surrounding the swirl effect sometimes referred to as the 5th harmonic analysis of AC induction motor rotors. This research showed that the phase shift in the air-gap flux density surrounding a broken bar will result in pole-pass frequency sidebands at the 5th harmonic of line frequency. And of equal importance, it showed that these sidebands are less affected by other non-rotor bar related anomalies unlike the case with sidebands around line frequency. As an example, asymmetries like bearing eccentricity or an out of round rotor can mask or give a false indication of a rotor bar issue when looking at the sidebands around line frequency, but again, have little effect on the sideband clarity at the 5th harmonic of line frequency.

To see a case study discussing the swirl effect visit the PdMA YouTube Channel at:

Filed Under: Electric Motors

Motor Space Heaters

Depending on the environment and criticality of your electric motor, space heaters should be strongly considered if you want to ensure maximum reliability and expected motor life. When a motor is secured (de-energized) there is an initial increase in temperature due to the loss of cooling air. However, very quickly after shutdown the temperature of the motor windings will start to drop. Once the temperature falls below the dew point, air moisture will condensate on the windings and machined surfaces creating a conductive path for current to ground. This drop in resistance to ground due to the surface moisture contamination can cause a low state of reliability for the next startup and increase the chance of a failure. When selecting a space heater, a simple calculation can give you a ball park estimate for power requirements to remain above the dew point.

H = DL/35

Where:

H = Heater size in kW

D = Diameter in Feet

L = Length in Feet (between end bell centers)

To see the results of excessive moisture on a 2000HP electric motor visit the PdMA YouTube Channel at:

https://www.youtube.com/watch?v=9SG3lNm8u8w

Filed Under: Electric Motors

What’s causing your high motor current?

The most frequent concern about high current with a three-phase motor is high no-load current. But the broad issue of high no-load current isn’t the only three-phase motor issue to which plants should pay heed: High current with load and lower-than-expected no-load current are potential areas of concern, too. Let’s explore the sources of all of these.

High no-load current: Motor not rewound

One situation in which higher-than-expected no-load current can occur is with reconditioned motors. Although some motors with no-load currents above or below the guidelines may still be satisfactory, motors with no-load current outside of these ranges warrant further analysis.

When no-load current is high or low, consider the actual test operating voltage versus the motor’s rated voltage. If the applied voltage is not within 10% of the motor’s rated voltage, then the no-load current can be much higher or lower than expected. For example, test-operating a motor rated 200 volts on a 240-volt supply system is almost certain to result in relatively high no-load current.

A misconnection also can cause unusually high or low no-load current. For example, consider a 12-lead single voltage motor intended to be connected parallel-delta (Figure 1) for 460 volts. Because most 12-lead motors are dual-voltage, the motor could be mistakenly connected series-delta (Figure 2) for operation at 460 volts, which would result in exceptionally low no-load current. The solution is to connect the motor for parallel delta.

Click to read the full article and see the tables: https://www.plantservices.com/articles/2018/md-whats-causing-your-high-motor-current/

 

Filed Under: Electric Motors

Motor Reliability Commitment for 2018: Part II

Continuing with the January fresh start for a new year of commitments we will focus on motor efficiency best practices. The following are some considerations for best practice in optimizing your motor efficiency and overall power consumption:

  • Size your motor correctly.  Your motor operates much more efficiently when it is running above 60% of rated horsepower. The efficiency drops significantly when running below 50%.
  • Reliability before Efficiency.  No matter how efficient your motor is, if it is running in a reduced reliability state you risk a short life expectancy, which will eliminate any savings. Establish a predictive maintenance approach to test your electric motors on a routine basis.
  • Establish a Replacement Strategy.

○ Immediate Replacement – If a motor offers a quick return through energy savings it should be considered for immediate replacement. Examples include older inefficient motors that run continuously. Especially oversized motors.

○ After Failure Replacement – Motors offering only a moderate payback period can be replaced with a high efficiency motor at the time of failure.

○ No Replacement Necessary – Motors already exhibiting acceptable efficiency with an extended payback period should not be included in the replacement plan. Especially motors that run only intermittently.

System Efficiency vs. Motor Efficiency.  When evaluating electric motors for improved efficiency always look at the total system efficiency including the driven load for the best overall cost effective solution.

From our friends at pdma

Filed Under: Electric Motors

  • « Previous Page
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • Next Page »

Archives

  • June 2025
  • May 2025
  • April 2025
  • March 2025
  • February 2025
  • January 2025
  • November 2024
  • August 2024
  • June 2024
  • May 2024
  • April 2024
  • March 2024
  • January 2024
  • November 2023
  • October 2023
  • September 2023
  • August 2023
  • June 2023
  • May 2023
  • April 2023
  • February 2023
  • January 2023
  • December 2022
  • November 2022
  • October 2022
  • August 2022
  • July 2022
  • June 2022
  • May 2022
  • April 2022
  • March 2022
  • February 2022
  • January 2022
  • December 2021
  • November 2021
  • October 2021
  • September 2021
  • August 2021
  • July 2021
  • June 2021
  • April 2021
  • March 2021
  • February 2021
  • January 2021
  • December 2020
  • November 2020
  • October 2020
  • September 2020
  • August 2020
  • July 2020
  • June 2020
  • May 2020
  • April 2020
  • March 2020
  • February 2020
  • January 2020
  • December 2019
  • November 2019
  • October 2019
  • September 2019
  • August 2019
  • July 2019
  • June 2019
  • May 2019
  • April 2019
  • March 2019
  • February 2019
  • January 2019
  • December 2018
  • November 2018
  • October 2018
  • September 2018
  • August 2018
  • July 2018
  • June 2018
  • May 2018
  • April 2018
  • March 2018
  • February 2018
  • January 2018
  • December 2017
  • November 2017
  • October 2017
  • September 2017
  • August 2017
  • July 2017
  • May 2017
  • April 2017
  • March 2017
  • February 2017
  • January 2017
  • December 2016
  • November 2016
  • October 2016
  • September 2016
  • August 2016
  • July 2016
  • June 2016
  • May 2016
  • April 2016
  • March 2016
  • January 2016
  • December 2014
  • November 2014

Copyright © 2025 Decatur Industrial Electric - 217-428-6621